Rép. : Re: [Nagios-users] Powerware UPS

Serveur-Faucon Surveillance SrvFaucon at cslaval.qc.ca
Wed Apr 14 15:24:21 CEST 2004


I have some powerware with the SNMP/Web card. Here are my SNMP check commands.

I have included a little translation in English between "**", do not include thoses in the commands file :)


** input voltage that works with every snmp ups **

# AJOUT *** Ajout pour le VOLTAGE d'un UPS (SNMP UPS standard) en entree (upsinputvoltage)
# SNMP
define command{
        command_name     snmp_UPS_inputvoltage
        command_line     $USER1$/check_snmp -H $HOSTADDRESS$ -c 70:140 -C $ARG1$ -o .1.3.6.1.2.1.33.1.3.3.1.3.1 -l SNMPinputVoltage -u Volts -t $USER29$
        }


** Powerware only - temperature **

# AJOUT *** Ajout pour TEMPERATURE d'un UPS (PowerWare seulement)
# SNMP
define command{
        command_name     snmp_Pware_temp
        command_line     $USER1$/check_snmp -H $HOSTADDRESS$ -w $ARG1$ -c $ARG2$ -C $ARG3$ -o .1.3.6.1.4.1.534.1.6.1.0 -l SNMPTemperature -u Celcius -t $USER29$
        }


** UPS load, every snmp ups **

# AJOUT *** Ajout pour la charge (load) du UPS. (SNMP UPS standard)
# SNMP
define command{
        command_name     snmp_UPS_load
        command_line     $USER1$/check_snmp -H $HOSTADDRESS$ -w $ARG1$ -c $ARG2$ -C $ARG3$ -o .1.3.6.1.2.1.33.1.4.4.1.5.1 -l SNMPLoad -t $USER29$
        }


** ups status, every snmp ups. Not very usefull unless you know the return codes **

# AJOUT *** Ajout pour le STATUS d'un UPS PowerWare (output power). (SNMP UPS standard)
# SNMP
define command{
        command_name     snmp_UPS_BStatus
        command_line     $USER1$/check_snmp -H $HOSTADDRESS$ -C $ARG1$ -o .1.3.6.1.2.1.33.1.4.1.0 -l SNMPStatus -t $USER29$
        }


** powerware only - time remaning on battery in seconds **

# AJOUT *** Ajout Temps restant sur la pile d'un UPS PowerWare en SECONDES (PowerWare seulement)
# SNMP UPS
define command{
        command_name     snmp_Pware_PileSecRest
        command_line     $USER1$/check_snmp -H $HOSTADDRESS$ -C $ARG1$ -o .1.3.6.1.4.1.534.1.2.1.0 -w $ARG2$ -c $ARG3$ -l SNMPSecRestPWare -u sec -t $USER29$
        }


** every snmp ups, time remaning in minutes **

# AJOUT *** Temps restant sur la pile d'un UPS PowerWare en MINUTES (SNMP UPS standard)
# SNMP UPS
define command{
        command_name     snmp_UPS_PileMinRest
        command_line     $USER1$/check_snmp -H $HOSTADDRESS$ -C $ARG1$ -o .1.3.6.1.2.1.33.1.2.3.0 -w $ARG2$ -c $ARG3$ -l SNMPMinRestUPS -u min -t $USER29$
        }


** powerware only - OS version of the snmp/web card **

# AJOUT *** Version du OS sur la carte SNMP (PowerWare seulement)
# SNMP UPS
define command{
        command_name     snmp_PWare_VersionOS
        command_line     $USER1$/check_snmp -H $HOSTADDRESS$ -C $ARG1$ -o .1.3.6.1.4.1.534.1.1.3.0 -l SNMPVersionOS -t $USER29$
        }


** everything that does snmp, uptime of the snmp object **

# AJOUT *** Pour voir le sysuptime (sysuptime de la partie reseau) (tout ce qui fait du SNMP)
# SNMP
define command{
        command_name     snmp_sysuptime
        command_line     $USER1$/check_snmp -H $HOSTADDRESS$ -C $ARG1$ -o .1.3.6.1.2.1.1.3.0 -l SNMPuptime -t $USER29$
        }




**end**




---------------------------------------------------
Alexandre Racine
Montréal, Québec, Canada

>>> Subhendu Ghosh <sghosh at sghosh.org> 2004-04-07 09:05:01 >>>

No such plugin exists.  Powerware uses a proprietary serial protocol that
the folks at Network UPS Tools have not been able to integrate.

However, Powerware's LanSafe Monitoring application does provide a SNMP
sub-agent on Windows that can supports the standard UPS-MIB.  
(automatically installed if you already have SNMP running)
This assumes you are running the windows box as the LanSafe Controller.  
Only one UPS per windows snmp agent.

Alternately - if you have the Web/SNMP card - that supports the standard 
UPS-MIB as well.

-sg

On Wed, 7 Apr 2004, Jim Mozley wrote:

> Spencer L Horn wrote:
> 
> > Does anyone know off the top of there head of a decent plugin to monitor
> > Powerware ups's?
> 
> Did you check the archives?
> Did you check the contrib plugins? There is one there for apc ups that 
> could possibly be modified.
> Did you consider snmp; either traps or polling?
> 
> Jim Mozley
> 
> 
> -------------------------------------------------------
> This SF.Net email is sponsored by: IBM Linux Tutorials
> Free Linux tutorial presented by Daniel Robbins, President and CEO of
> GenToo technologies. Learn everything from fundamentals to system
> administration.http://ads.osdn.com/?ad_id=1470&alloc_id=3638&op=click
> _______________________________________________
> Nagios-users mailing list
> Nagios-users at lists.sourceforge.net 
> https://lists.sourceforge.net/lists/listinfo/nagios-users 
> ::: Please include Nagios version, plugin version (-v) and OS when reporting any issue. 
> ::: Messages without supporting info will risk being sent to /dev/null
> 

-- 




-------------------------------------------------------
This SF.Net email is sponsored by: IBM Linux Tutorials
Free Linux tutorial presented by Daniel Robbins, President and CEO of
GenToo technologies. Learn everything from fundamentals to system
administration.http://ads.osdn.com/?ad_id=1470&alloc_id=3638&op=click
_______________________________________________
Nagios-users mailing list
Nagios-users at lists.sourceforge.net 
https://lists.sourceforge.net/lists/listinfo/nagios-users 
::: Please include Nagios version, plugin version (-v) and OS when reporting any issue. 
::: Messages without supporting info will risk being sent to /dev/null


-------------------------------------------------------
This SF.Net email is sponsored by: IBM Linux Tutorials
Free Linux tutorial presented by Daniel Robbins, President and CEO of
GenToo technologies. Learn everything from fundamentals to system
administration.http://ads.osdn.com/?ad_id70&alloc_id638&op=click
_______________________________________________
Nagios-users mailing list
Nagios-users at lists.sourceforge.net
https://lists.sourceforge.net/lists/listinfo/nagios-users
::: Please include Nagios version, plugin version (-v) and OS when reporting any issue. 
::: Messages without supporting info will risk being sent to /dev/null





More information about the Users mailing list