ups oids that might help
shadih rahman
shadhin71 at gmail.com
Mon Apr 27 23:02:34 CEST 2009
I had to spend a lot of time looking for oids on liebert and on apc upses.
I just wanted to share it with the group.
*Liebert oids
*
Description
OID
Definition MIB SOURCE
BupsBatteryVoltage
1.3.6.1.2.1.33.1.2.5 The magnitude of the present battery
voltage. RFC1628_UPS_MIB.MIB
upsInputNumLines
1.3.6.1.2.1.33.1.3.2 The number of input lines utilized in
this device. RFC1628_UPS_MIB.MIB
upsInputVoltage
1.3.6.1.2.1.33.1.3.3.1.3 The magnitude of the present input
voltage. RFC1628_UPS_MIB.MIB
upsInputFrequency
1.3.6.1.2.1.33.1.3.3.1.2 The present input
frequency. RFC1628_UPS_MIB.MIB
upsOutputNumLines
1.3.6.1.2.1.33.1.4.3 The number of output lines utilized
in this device RFC1628_UPS_MIB.MIB
upsOutputFrequency
1.3.6.1.2.1.33.1.4.2 The present output
frequency. RFC1628_UPS_MIB.MIB
upsOutputVoltage
1.3.6.1.2.1.33.1.4.4.1.2 The present output
voltage. RFC1628_UPS_MIB.MIB
upsOutputCurrent
1.3.6.1.2.1.33.1.4.4.1.3 The present output
current. RFC1628_UPS_MIB.MIB
upsBypassNumLines
1.3.6.1.2.1.33.1.5.2 The number of bypass lines utilized
in this device RFC1628_UPS_MIB.MIB
upsBypassFrequency
1.3.6.1.2.1.33.1.5.1 The present bypass
frequency. RFC1628_UPS_MIB.MIB
upsBypassVoltage
1.3.6.1.2.1.33.1.5.3.1.2 The present bypass
voltage. RFC1628_UPS_MIB.MIB
lgpPwrBatteryVoltage
1.3.6.1.4.1.476.1.42.3.5.2.4.1.4.1 The present battery
voltage. LIEBERT_GP_POWER.MIB
lgpPwrBatteryNominalVoltage
1.3.6.1.4.1.476.1.42.3.5.2.4.1.6.1 The present battery
voltage. LIEBERT_GP_POWER.MIB
lgpPwrBatteryCapacity
1.3.6.1.4.1.476.1.42.3.5.1.19 The present percentage of battery
capacity. LIEBERT_GP_POWER.MIB
lgpPwrMeasurementPointVAPercent
1.3.6.1.4.1.476.1.42.3.5.2.2.1.11 The percentage of the rated apparent
AC power of the power LIEBERT_GP_POWER.MIB
source indicated by 'lgpPwrMeasurementPointId' in the
corresponding row in the lgpPwrMeasurementPointTable.
lgpPwrMeasurementPointNomCurrent
1.3.6.1.4.1.476.1.42.3.5.2.2.1.14 The nominal or configured/expected
current of the power LIEBERT_GP_POWER.MIB
point indicated by 'lgpPwrMeasurementPointId' in the
corresponding row in the lgpPwrMeasurementPointTable.
lgpPwrMeasurementPointNomVA
1.3.6.1.4.1.476.1.42.3.5.2.2.1.16 The nominal or configured/expected
apparent AC power for LIEBERT_GP_POWER.MIB
the power source indicated by 'lgpPwrMeasurementPointId'
in the corresponding row in the lgpPwrMeasurementPointTable.
lgpPwrMeasurementPointNomPowerFactor
1.3.6.1.4.1.476.1.42.3.5.2.2.1.15 The nominal or configured/expected
power factor of the power LIEBERT_GP_POWER.MIB
point indicated by 'lgpPwrMeasurementPointId' in the
corresponding row in the lgpPwrMeasurementPointTable.
lgpPwrLineMeasurementCurrent
1.3.6.1.4.1.476.1.42.3.5.2.3.1.6 Output Current
L1 LIEBERT_GP_POWER.MIB
maximum input voltage
1.3.6.1.4.1.476.1.42.3.5.2.3.1.16.1.1 maximum input voltage recorded
since LIEBERT_GP_POWER.MIB
'lgpPwrStatisticsReset' was executed.
minumum input voltage
1.3.6.1.4.1.476.1.42.3.5.2.3.1.17.1.1 minimum input voltage recorded
since LIEBERT_GP_POWER.MIB
'lgpPwrStatisticsReset' was executed.
maximum output voltage
1.3.6.1.4.1.476.1.42.3.5.2.3.1.16.3.1 maximum output voltage recorded
since LIEBERT_GP_POWER.MIB
'lgpPwrStatisticsReset' was executed.
minumum output voltage
1.3.6.1.4.1.476.1.42.3.5.2.3.1.17.3.1 minimum output voltage recorded
since LIEBERT_GP_POWER.MIB
'lgpPwrStatisticsReset' was executed.
Output Real Load in W
1.3.6.1.4.1.476.1.42.3.5.2.2.1.8.3 output real Load in
Wattage LIEBERT_GP_POWER.MIB
Output Apparant Load in VA
1.3.6.1.4.1.476.1.42.3.5.2.2.1.7.3 output real Load in
volt-ampere LIEBERT_GP_POWER.MIB
Ambient Temperature in centigrade
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.3.1 Ambient temperature in degree
centigrade LIEBERT_GP_POWER.MIB
*
APC well known OIDs *
Description
OID
Definition MIB SOURCE
upsAdvBatteryCapacity 1.3.6.1.4.1.318.1.1.1.2.2.1
The remaining battery capacity expressed in percent POWERNET-MIB
of full capacity.
upsAdvBatteryTemperature 1.3.6.1.4.1.318.1.1.1.2.2.2
The current internal UPS temperature expressed in Celsius. POWERNET-MIB
upsAdvInputLineVoltage 1.3.6.1.4.1.318.1.1.1.3.2.1
The current utility line voltage in VAC. POWERNET-MIB
upsAdvInputMaxLineVoltage 1.3.6.1.4.1.318.1.1.1.3.2.2
The maximum utility line voltage in VAC over the POWERNET-MIB
previous 1 minute period.
upsAdvInputMinLineVoltage 1.3.6.1.4.1.318.1.1.1.3.2.3
The minimum utility line voltage in VAC over the previous POWERNET-MIB
1 minute period.
upsAdvInputFrequency 1.3.6.1.4.1.318.1.1.1.3.2.4
The current input frequency to the UPS system in Hz. POWERNET-MIB
upsAdvOutputVoltage 1.3.6.1.4.1.318.1.1.1.4.2.1
The output voltage of the UPS system in VAC. POWERNET-MIB
upsAdvOutputFrequency 1.3.6.1.4.1.318.1.1.1.4.2.2
The current output frequency of the UPS system in Hz. POWERNET-MIB
upsAdvOutputLoad 1.3.6.1.4.1.318.1.1.1.4.2.3
The current UPS load expressed in percent of rated capacity. POWERNET-MIB
--
Cordially,
Shadhin Rahman
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <https://www.monitoring-lists.org/archive/users/attachments/20090427/61aada39/attachment.html>
-------------- next part --------------
------------------------------------------------------------------------------
Crystal Reports - New Free Runtime and 30 Day Trial
Check out the new simplified licensign option that enables unlimited
royalty-free distribution of the report engine for externally facing
server and web deployment.
http://p.sf.net/sfu/businessobjects
-------------- next part --------------
_______________________________________________
Nagios-users mailing list
Nagios-users at lists.sourceforge.net
https://lists.sourceforge.net/lists/listinfo/nagios-users
::: Please include Nagios version, plugin version (-v) and OS when reporting any issue.
::: Messages without supporting info will risk being sent to /dev/null
More information about the Users
mailing list