I had to spend a lot of time looking for oids on liebert and on apc upses. I just wanted to share it with the group.<br><br><br><br><b>Liebert oids<br></b><br><br> Description OID Definition MIB SOURCE<br>
BupsBatteryVoltage 1.3.6.1.2.1.33.1.2.5 The magnitude of the present battery voltage. RFC1628_UPS_MIB.MIB<br> upsInputNumLines 1.3.6.1.2.1.33.1.3.2 The number of input lines utilized in this device. RFC1628_UPS_MIB.MIB<br>
upsInputVoltage 1.3.6.1.2.1.33.1.3.3.1.3 The magnitude of the present input voltage. RFC1628_UPS_MIB.MIB<br> upsInputFrequency 1.3.6.1.2.1.33.1.3.3.1.2 The present input frequency. RFC1628_UPS_MIB.MIB<br>
upsOutputNumLines 1.3.6.1.2.1.33.1.4.3 The number of output lines utilized in this device RFC1628_UPS_MIB.MIB<br> upsOutputFrequency 1.3.6.1.2.1.33.1.4.2 The present output frequency. RFC1628_UPS_MIB.MIB<br>
upsOutputVoltage 1.3.6.1.2.1.33.1.4.4.1.2 The present output voltage. RFC1628_UPS_MIB.MIB<br> upsOutputCurrent 1.3.6.1.2.1.33.1.4.4.1.3 The present output current. RFC1628_UPS_MIB.MIB<br>
upsBypassNumLines 1.3.6.1.2.1.33.1.5.2 The number of bypass lines utilized in this device RFC1628_UPS_MIB.MIB<br> upsBypassFrequency 1.3.6.1.2.1.33.1.5.1 The present bypass frequency. RFC1628_UPS_MIB.MIB<br>
upsBypassVoltage 1.3.6.1.2.1.33.1.5.3.1.2 The present bypass voltage. RFC1628_UPS_MIB.MIB<br> lgpPwrBatteryVoltage 1.3.6.1.4.1.476.1.42.3.5.2.4.1.4.1 The present battery voltage. LIEBERT_GP_POWER.MIB<br>
lgpPwrBatteryNominalVoltage 1.3.6.1.4.1.476.1.42.3.5.2.4.1.6.1 The present battery voltage. LIEBERT_GP_POWER.MIB<br> lgpPwrBatteryCapacity 1.3.6.1.4.1.476.1.42.3.5.1.19 The present percentage of battery capacity. LIEBERT_GP_POWER.MIB<br>
lgpPwrMeasurementPointVAPercent 1.3.6.1.4.1.476.1.42.3.5.2.2.1.11 The percentage of the rated apparent AC power of the power LIEBERT_GP_POWER.MIB<br> source indicated by 'lgpPwrMeasurementPointId' in the <br>
corresponding row in the lgpPwrMeasurementPointTable.<br> lgpPwrMeasurementPointNomCurrent 1.3.6.1.4.1.476.1.42.3.5.2.2.1.14 The nominal or configured/expected current of the power LIEBERT_GP_POWER.MIB<br>
point indicated by 'lgpPwrMeasurementPointId' in the <br> corresponding row in the lgpPwrMeasurementPointTable.<br>
lgpPwrMeasurementPointNomVA 1.3.6.1.4.1.476.1.42.3.5.2.2.1.16 The nominal or configured/expected apparent AC power for LIEBERT_GP_POWER.MIB<br> the power source indicated by 'lgpPwrMeasurementPointId' <br>
in the corresponding row in the lgpPwrMeasurementPointTable. <br> lgpPwrMeasurementPointNomPowerFactor 1.3.6.1.4.1.476.1.42.3.5.2.2.1.15 The nominal or configured/expected power factor of the power LIEBERT_GP_POWER.MIB<br>
point indicated by 'lgpPwrMeasurementPointId' in the <br> corresponding row in the lgpPwrMeasurementPointTable.<br>
lgpPwrLineMeasurementCurrent 1.3.6.1.4.1.476.1.42.3.5.2.3.1.6 Output Current L1 LIEBERT_GP_POWER.MIB<br> maximum input voltage 1.3.6.1.4.1.476.1.42.3.5.2.3.1.16.1.1 maximum input voltage recorded since LIEBERT_GP_POWER.MIB<br>
'lgpPwrStatisticsReset' was executed.<br> minumum input voltage 1.3.6.1.4.1.476.1.42.3.5.2.3.1.17.1.1 minimum input voltage recorded since LIEBERT_GP_POWER.MIB<br>
'lgpPwrStatisticsReset' was executed. <br> maximum output voltage 1.3.6.1.4.1.476.1.42.3.5.2.3.1.16.3.1 maximum output voltage recorded since LIEBERT_GP_POWER.MIB<br>
'lgpPwrStatisticsReset' was executed.<br> minumum output voltage 1.3.6.1.4.1.476.1.42.3.5.2.3.1.17.3.1 minimum output voltage recorded since LIEBERT_GP_POWER.MIB<br>
'lgpPwrStatisticsReset' was executed. <br> Output Real Load in W 1.3.6.1.4.1.476.1.42.3.5.2.2.1.8.3 output real Load in Wattage LIEBERT_GP_POWER.MIB<br>
Output Apparant Load in VA 1.3.6.1.4.1.476.1.42.3.5.2.2.1.7.3 output real Load in volt-ampere LIEBERT_GP_POWER.MIB<br> Ambient Temperature in centigrade 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.3.1 Ambient temperature in degree centigrade LIEBERT_GP_POWER.MIB<br>
<b><br> APC well known OIDs </b><br><br> Description OID Definition MIB SOURCE<br> upsAdvBatteryCapacity 1.3.6.1.4.1.318.1.1.1.2.2.1 The remaining battery capacity expressed in percent POWERNET-MIB<br>
of full capacity. <br> upsAdvBatteryTemperature 1.3.6.1.4.1.318.1.1.1.2.2.2 The current internal UPS temperature expressed in Celsius. POWERNET-MIB<br>
upsAdvInputLineVoltage 1.3.6.1.4.1.318.1.1.1.3.2.1 The current utility line voltage in VAC. POWERNET-MIB<br> upsAdvInputMaxLineVoltage 1.3.6.1.4.1.318.1.1.1.3.2.2 The maximum utility line voltage in VAC over the POWERNET-MIB<br>
previous 1 minute period.<br> upsAdvInputMinLineVoltage 1.3.6.1.4.1.318.1.1.1.3.2.3 The minimum utility line voltage in VAC over the previous POWERNET-MIB<br>
1 minute period.<br> upsAdvInputFrequency 1.3.6.1.4.1.318.1.1.1.3.2.4 The current input frequency to the UPS system in Hz. POWERNET-MIB<br>
upsAdvOutputVoltage 1.3.6.1.4.1.318.1.1.1.4.2.1 The output voltage of the UPS system in VAC. POWERNET-MIB<br> upsAdvOutputFrequency 1.3.6.1.4.1.318.1.1.1.4.2.2 The current output frequency of the UPS system in Hz. POWERNET-MIB<br>
upsAdvOutputLoad 1.3.6.1.4.1.318.1.1.1.4.2.3 The current UPS load expressed in percent of rated capacity. POWERNET-MIB<br clear="all"><br>-- <br>Cordially,<br>Shadhin Rahman<br>